PRODUCTS
Recloser(Solid)
Feature
Epoxy mold insulation and vaccum interruption
Stainless steel and double sealing
Simple operation and maintenance
Climate-independent
| Rated voltage | 24kV | ||
| Rated current | 630A | ||
| Rated power frequency | 50/60Hz | ||
| Rated short-time withstand current | 16kA | ||
| Fault make capacity (Peak) | 41.6kA | ||
| Fault make capacity (RMS) | 16kA | ||
| Operating time | 0.1 / 0.05s | ||
| Mechanical endurance | 10,000 | ||
| Dielectric test | Lightning Impulse | 125kV | |
| Power frequency | 50kV | ||
| Reclosing | Reclose interval 1st | 0.3 ~ 180s (step:0.1) | |
| Reclose interval 2nd | 1 ~ 180s (step:1) | ||
| Reclose interval 3rd | 1 ~ 180s (step:1) | ||
| Reclose interval 4th | 1 ~ 180s (step:1) | ||
| Reset time | 3 ~ 180s (step:1) | ||
| Dust and Water Proof | Tank | IP 67 | |