PRODUCTS
Sectionalizer

Feature
SF6 gas insulation and interruption
Stainless steel and double sealing
Simple operation and maintenance
Climate-independent
Rated voltage | 25.8kV | ||
Rated current | 630A | ||
Rated power frequency | 50/60Hz | ||
Rated short-time withstand current | 12.5kA/1sec | ||
Rated making current | 32.5kA peak, 5C | ||
Ambient temperature | -25 ~ 70℃ | ||
Maximum altitude | 2,000 M | ||
Mechanical endurance | 5,000 CO | ||
Dielectric test | Lightning Impulse | 150kV | |
Power frequency | 60kV | ||
Make and break test | Active load | 630A | |
Closed loop | 630A | ||
Cable charging | 25A | ||
Line charging | 1.5A | ||
Gas leak test | Gas leak | Less than 0.1% per year | |
Rated filling pressure | 0.1 Mpa | ||
Dust and Water Proof | Tank | IP 65 | |
Control cabinet | IP 54 |